The proposed measure would direct Virginia's air pollution board to limit data center generator use and require cleaner equipment for certain sites.
Data centers could use Tier 2 generators only during sudden, unforeseeable outages; planned outages would not qualify.
Data centers that applied for an air permit before July 1, 2026, would have to retrofit at least 20 percent of their Tier 2 generators each year to meet Tier 4 equivalent or better emissions.
Data centers whose site plans lacked local approval by July 1, 2026, would have to use Tier 4 equivalent or better generators at those sites.
The proposed measure would direct the State Air Pollution Control Board to limit when data centers could use Tier 2 generators. The limit would cover data center emergency generators rated Tier 2. Use would be limited to sudden and unforeseeable outage events; planned outages would not qualify.
The proposed measure would require annual retrofits to some data centers' Tier 2 generator fleets. This would apply to data centers that applied for an air permit before July 1, 2026. Each year, at least 20 percent of the Tier 2 fleet would have to be retrofitted to meet Tier 4 equivalent or better emissions. The yearly retrofits would continue for five years or until the entire fleet meets that emissions level, whichever comes first.
The proposed measure would require certain data center sites to have Tier 4 equivalent or better generators. This would apply where a locality had not approved the data center site plan by July 1, 2026. The approval cutoff is July 1, 2026.
No hearings or votes scheduled.